Carrier Furnace Code 43: Pressure Switch Calibration Fault

Last updated Sep 15, 2026 Β· By fixme.vip Editorial

Carrier Furnace: Code 43
Applies to: Carrier variable-speed condensing furnaces (e.g. Infinity/Performance 96/98 series) with a self-calibrating control board and low-pressure switch. On some board legends the code number and meaning vary β€” always confirm against the label inside your blower door.
Typical repair cost: $0 DIY – $1,200 if the inducer assembly or control board needs replacement β€” compare free local quotes

Get this fixed by a local pro

Free, no-obligation quotes from licensed HVAC technicians in your area. Compare up to 3 estimates before anyone visits.

Get free local quotes

Carrier furnace code 43: what it means

Carrier Furnace Code 43 is a pressure switch calibration fault. On variable-speed condensing furnaces, the control board ramps the inducer motor to specific speeds and watches the low-pressure switch to confirm it opens and closes at the expected points. This β€œcalibration” lets the board account for real-world venting resistance.

If the switch changes state at the wrong inducer speed β€” too early, too late, or not at all β€” the board cannot complete calibration and posts Code 43. The root cause is almost always venting, the pressure-switch tubing, or the switch itself, not the gas or ignition system.

Because the furnace typically will not fire until calibration succeeds, this is a pro-level fault: it protects against operating with restricted or unsafe venting. The board usually retries on the next heat call, but the code will keep returning until the physical cause is corrected.

Note: exact code numbering and wording differ between board generations. Confirm the meaning on the fault-code legend printed inside your blower compartment door before ordering parts.

Carrier furnace code 43: common causes, ranked by probability

  1. Blocked or restricted vent/intake termination β€” snow, ice, leaves, insect nests, or a bird screen clogged at the exterior PVC pipes changes the pressure the inducer sees.
  2. Pressure-switch tubing problems β€” cracked, kinked, disconnected, or condensate-filled hoses give the switch a false reading during the calibration sweep.
  3. Blocked or sagging condensate drainage β€” water backing up in the collector box or trap raises venting resistance and skews calibration.
  4. Failed or out-of-spec low-pressure switch β€” a switch that trips at the wrong point (or sticks) can’t be calibrated against.
  5. Inducer motor weak or out of range β€” a variable-speed inducer that can’t hit its target speeds prevents the board from finding a valid calibration.
  6. Vent pipe sizing/length or joint leaks β€” improper installation or a loose coupling changes system pressure enough to fail calibration.
  7. Control board fault β€” least common; the board’s calibration logic or sensing circuit is faulty.

How to fix Carrier furnace code 43: safe checks first

These are the only steps a homeowner should perform:

If Code 43 returns after one reset, stop and call a technician. Do not open the cabinet or touch the pressure switch, tubing, or inducer.

How a technician will diagnose it

A qualified tech will typically:

Sanity check: a good quote names the specific failed component after testing, not a blanket board swap.

Symptom, cause and what to do

SymptomLikely causeDIY actionTechnician job
Code 43, furnace won’t fireBlocked vent/intake terminationsClear visible snow/debris from outside pipesInspect full venting, remeasure draft
Code 43 after cold/windy weatherIce or nest in exterior pipesClear only what’s visible outsideInspect terminations, verify slope/length
Code 43 with water near furnaceBlocked condensate drainClear accessible drain endClean collector box and trap
Code 43, inducer runs but won’t validateCracked/kinked/full switch tubingNone β€” internalInspect and replace tubing
Code 43 persists after clearing ventsFailed pressure switchNone β€” internalManometer test, replace switch
Code 43 with weak/noisy inducerInducer out of speed rangeNone β€” internalTest and replace inducer motor
Code 43 with all else goodControl board faultNone β€” internalVerify sensing circuit, replace board

Carrier furnace code 43 repair cost

Honest US ranges (parts + labor; regional variation applies):

Simple blockages cost little; component replacement is where bills climb. Always get the failed part identified by test before authorizing an inducer assembly or a board.

Safety first: anything beyond filters, batteries, and visual checks on gas-burning equipment should be handled by a licensed technician. Repeatedly resetting a locked-out unit can mask a dangerous fault. When in doubt, get a pro.

Frequently asked questions

Does Carrier Code 43 reset by itself?

On most variable-speed boards the furnace retries calibration on the next call for heat, but a persistent fault holds until the underlying venting, tubing or switch problem is fixed. Repeated cycling without repair is a symptom, not a solution.

Can I fix Code 43 myself?

Only the safe basics β€” check for blocked vent terminations, a clogged condensate line and a dirty filter. Calibration involves the inducer, pressure switch and tubing inside the cabinet, which is technician work.

Is Code 43 dangerous to run with?

The furnace usually will not fire until it calibrates, which is a protective behavior. Do not bypass the pressure switch or force operation; a calibration fault can point to a venting blockage that must be corrected safely.

Different code on your furnace? Look it up β€” and if we haven't covered it yet, telling us is how it gets written next.