Lennox · Furnace

Lennox Furnace Blower Won't Shut Off: Causes & Fixes

Last updated Sep 29, 2026 · By fixme.vip Editorial

Lennox Furnace: Blower won't shut off
Applies to: Most Lennox gas furnaces (Merit, Elite, Signature) using SureLight integrated ignition control boards; older units may use a different OEM-supplied board, and fan-off delay options and terminal behavior vary by board.
Typical repair cost: $0 DIY – $1,200 if the control board fails

Parts & tools for this fix

As an Amazon Associate, fixme.vip earns from qualifying purchases. Prices and availability are on Amazon.

Lennox furnace blower won't shut off: what it means

“Blower won’t shut off” is not a numbered Lennox fault code — it’s a behavior. Your indoor blower motor runs continuously instead of stopping after the heating cycle ends. On most Lennox gas furnaces (Merit, Elite, and Signature series using SureLight integrated ignition control boards — older units may use a different OEM-supplied board), the blower is commanded by the control board through a fan relay, and it’s told when to run by the thermostat and by the furnace’s own safety and timing logic.

A short run-on period is normal and by design: after the burners shut off, the board keeps the blower running for a fan-off delay (typically 60–180 seconds) to pull remaining heat off the heat exchanger. Fan-off delay options and terminal behavior vary by board — some are adjustable via dip switches or a jumper, some are not. If the blower runs longer than the delay your board is set for — or never stops at all — something is keeping the fan circuit energized.

Because this is a behavior rather than a lockout code, there is no auto-reset or hold state to report. The blower simply follows whatever is telling it to run.

Lennox furnace blower won't shut off: common causes, ranked by probability

  1. Thermostat fan set to ON instead of AUTO. This is by far the most common cause. In ON mode the thermostat energizes the G (fan) terminal continuously, so the blower runs 24/7 regardless of heating demand. This is a setting, not a fault.
  2. Open high-limit switch. If the heat exchanger overheats (often from a dirty filter or blocked airflow), the limit switch opens, shuts off the gas, and keeps the blower running continuously to cool the furnace. The fan running non-stop is the furnace protecting itself — and unlike the other causes, there is a real overheating condition behind it.
  3. Thermostat wiring or a failing thermostat holding G energized. A shorted G-to-R connection, a wiring fault, or a defective thermostat can keep the fan circuit powered even in AUTO.
  4. Stuck or welded fan relay on the control board. The relay contacts can weld closed, leaving the blower circuit permanently energized even after the board commands it off.
  5. Failed control board. A board with faulty fan-timing logic or damaged output circuitry may never de-energize the blower.
  6. Fan-off delay set too long. On boards where the delay is adjustable, a setting at the maximum can make a normal run-on look like a failure — the blower does eventually stop, just after several minutes.

Causes 2 and 4–6 require a technician (you can and should check the filter and vents yourself for cause 2). Note that gas-supply and ignition faults are not causes here — those belong to Lennox ignition and flame-proving codes.

How to fix Lennox furnace blower won't shut off: safe checks first

Do not open the furnace cabinet, test the relay, or touch any wiring — those steps are for a technician. And if the blower is running constantly while the furnace produces no heat, don’t keep running the furnace normally; that pattern points at an overheating/airflow problem that needs to be diagnosed.

How a technician will diagnose it

A qualified tech will typically:

  1. Verify the thermostat command. They’ll check whether G (fan) is being energized by the thermostat and confirm the fan setting and wiring.
  2. Check the high-limit switch. Using a multimeter, they’ll test whether the limit is open (which forces continuous blower operation) and investigate why — dirty filter, blower issue, or a failed limit.
  3. Test the fan relay on the control board. They’ll confirm whether the relay contacts have welded closed by checking continuity with the board de-energized.
  4. Inspect the control board outputs. If the thermostat and limit are fine and the relay isn’t stuck, they’ll evaluate the board’s fan-timing logic and output circuit.
  5. Verify the fan-off delay setting. They’ll check the dip switches or jumper, where the board provides them, against the Lennox spec to rule out an over-long but normal run-on.

A reasonable quote names the specific failed part — thermostat, limit switch, or control board — not a vague “electrical problem.”

Symptom, cause and what to do

SymptomLikely causeDIY actionTechnician job
Blower runs 24/7, heat works normallyThermostat fan set to ONSwitch fan to AUTOVerify thermostat wiring if AUTO doesn’t help
Blower runs constantly, no heatOpen high-limit from overheatingReplace filter, open vents, stop normal useTest limit, find airflow cause, replace limit
Blower never stops even in AUTOStuck/welded fan relayCycle breaker onceTest and replace fan relay or control board
Blower runs several minutes then stopsLong fan-off delay (normal or over-set)None neededAdjust dip switch/jumper if adjustable and too long
Erratic fan behaviorFailing thermostat or low batteriesReplace batteriesReplace thermostat, check G wiring
Blower runs after clean filter + AUTOControl board faultCycle breaker onceDiagnose and replace control board

Lennox furnace blower won't shut off repair cost

The good news: the single most common cause (fan set to ON) costs nothing to fix.

Lennox alert-code numbering and meanings vary by furnace and control board — confirm any code you see against the installation or service literature for your specific unit before acting on it.

Safety first: anything beyond filters, batteries, and visual checks on gas-burning equipment should be handled by a licensed technician. Repeatedly resetting a locked-out unit can mask a dangerous fault. When in doubt, get a pro.

Rather not DIY it?

Free, no-obligation quotes from licensed HVAC technicians in your area. Compare up to 3 estimates before anyone visits.

Get free local quotes

Frequently asked questions

Is it bad to let the blower run constantly?

If the blower is running non-stop simply because the thermostat fan is set to ON, it isn't dangerous — it just drives up your electric bill and can wear the motor faster. But if the blower runs constantly and you are getting no heat, the high limit may be open because the furnace has been overheating. In that case stop using the furnace normally and have the airflow problem diagnosed before running it again.

Why does my Lennox blower keep running after the heat stops?

A short run-on of 60 to 180 seconds after heating is normal — that is the fan-off delay cooling the heat exchanger. If it never stops, suspect the thermostat fan setting, an open limit switch, or a stuck relay.

Can I fix a blower that won't shut off myself?

You can check the thermostat fan setting (AUTO vs ON), replace batteries, swap the filter, and cycle the breaker. Anything inside the cabinet — relays, limit switches, wiring, the control board — is a technician job.

Will turning off the furnace at the breaker stop the blower?

Yes, cutting power at the breaker or furnace switch stops the blower immediately. If the blower restarts and won't shut off once power is restored, the underlying fault is still present and needs diagnosis.

Different code on your furnace? Look it up — and if we haven't covered it yet, telling us is how it gets written next.