Lennox Β· Furnace

Lennox Furnace Code E206: Gas Valve Relay Fix & Cost

Last updated Sep 23, 2026 Β· By fixme.vip Editorial

Lennox Furnace: Code E206
Applies to: Two-stage and modulating Lennox gas furnaces with communicating (iComfort-capable) integrated controls that display numeric E-codes on the board's alert/7-segment display β€” for example SLP98 and EL296 units. Non-communicating SureLight boards, such as those used in Merit-series furnaces, report faults as LED flash/blink patterns rather than an "E206" display, so this code text will not appear on them. Exact legend text may vary by board revision β€” always confirm against the diagnostic label inside your unit.
Typical repair cost: $0 DIY reset – $1,200 if the integrated control board is replaced β€” compare free local quotes

Get this fixed by a local pro

Free, no-obligation quotes from licensed HVAC technicians in your area. Compare up to 3 estimates before anyone visits.

Get free local quotes

Lennox furnace code E206: what it means

Lennox Code E206 means the integrated control is reporting a second-stage gas valve relay failure on a two-stage furnace. On two-stage and modulating furnaces, the control energizes separate first-stage (low fire) and second-stage (high fire) circuits at the gas valve; E206 is the control’s report that the second-stage relay function has failed.

That is the extent of what the code itself tells you. It does not identify why the relay circuit failed β€” that is what the diagnosis below is for. Because the reported fault is inside the control and its low-voltage circuitry, E206 is pro-level work.

In practice the furnace may still light and run on first stage but will not deliver high fire. If the code clears on a power cycle and then returns on the next high-fire call, the underlying problem has not been fixed. Legend wording and reset behavior can vary by board revision β€” confirm against the label inside your unit.

Lennox furnace code E206: common causes, ranked by probability

These are the possibilities a technician works through. The code names the failed function, not the root cause.

  1. Failed second-stage relay / control board β€” the most common finding. Worn or damaged relay contacts, a failed driver circuit, or board damage from a voltage surge all end in the same repair: the integrated control board is replaced.
  2. Damaged or corroded gas-valve harness / connector β€” a poor connection or damaged insulation on the second-stage lead is checked and ruled out before the board is condemned. Repairable if the board itself tests good.
  3. Second-stage gas valve problem β€” the second-stage coil and the valve itself are tested to rule them out as a contributor. If the valve is at fault, it is replaced.
  4. Water or debris intrusion on the board β€” condensate leaks or rodent damage near the control can corrode the board and its connections.

How to fix Lennox furnace code E206: safe checks first

These are the only steps a homeowner should attempt. Do not open the burner compartment, remove interior panels, or touch wiring.

Do not repeatedly reset a furnace that keeps re-logging E206 β€” repeated resets will not repair the reported fault.

How a technician will diagnose it

A qualified tech will:

  1. Read the fault history on the control to see how often E206 has occurred and whether it’s intermittent or persistent.
  2. Inspect the gas-valve harness and connectors for corrosion, loose pins, or damaged insulation on the second-stage lead.
  3. Measure the second-stage output with a multimeter during a high-fire call to see whether the control energizes the circuit.
  4. Test the second-stage gas valve coil resistance to rule the valve in or out.
  5. Check incoming line and 24 VAC to confirm the control is getting clean, stable power.
  6. Confirm the control itself β€” if the harness and valve test good but the second stage will not switch, the integrated control board is condemned and replaced.

A good quote should identify which component failed β€” the board, the harness, or the valve β€” not simply swap parts blindly.

Symptom, cause and what to do

SymptomLikely causeDIY actionTechnician job
Furnace runs on low fire only, weak heat on cold daysSecond stage not being energizedVerify thermostat and filter; one resetTest second-stage output, replace control board if confirmed
E206 returns immediately after resetPersistent relay/board failureStop resetting; call proReplace integrated control board
Intermittent E206, works some daysLoose or corroded harness, or intermittent board faultNote frequency and dates for the techInspect/repair gas-valve harness, retest second stage
E206 with no high firePossible second-stage valve or coil problemNoneTest coil and valve, replace if faulty
E206 after a water leak near the unitCorrosion on the control or connectionsClear the external condensate blockageInspect for water damage, replace board if needed

Lennox furnace code E206 repair cost

Honest US ranges, parts and labor combined:

Board replacement is the most common outcome for a genuine E206. If your furnace is under Lennox parts warranty, the board itself may be covered, leaving only labor.

Other Lennox code pages you may need. Check the meaning of each against the diagnostic legend inside your own unit, since wording varies by board revision:

Safety first: anything beyond filters, batteries, and visual checks on gas-burning equipment should be handled by a licensed technician. Repeatedly resetting a locked-out unit can mask a dangerous fault. When in doubt, get a pro.

Frequently asked questions

Can I fix Lennox Code E206 myself?

No. E206 is the control reporting a second-stage gas valve relay failure. Diagnosis and any repair require opening the cabinet and testing live circuits, which is licensed technician work.

Will my furnace still run with Code E206?

Often it will run on first stage (low fire) but cannot switch to second stage (high fire), so you may notice weaker heat on very cold days. Some units may stop heating entirely until repaired. Behavior varies by model and board revision.

Does Code E206 reset on its own?

Treat it as a fault that needs service. If it clears after a power cycle but comes back on the next high-fire call, the problem is still present and a technician needs to look at it.

Different code on your furnace? Look it up β€” and if we haven't covered it yet, telling us is how it gets written next.