Lennox Furnace Code E240: Low Flame Current Fix & Cost

Last updated Sep 26, 2026 · By fixme.vip Editorial

Lennox Furnace: Code E240
Applies to: Lennox and Dave Lennox Signature gas furnaces with SureLight integrated control boards (e.g. SLP98, EL296, ML196 and similar variable/two-stage models). Exact code text, code formats and thresholds vary by board revision; confirm against the diagnostic label and wiring diagram on your unit's cabinet.
Typical repair cost: $0 DIY reset – $750+ if the SureLight control board needs replacement — compare free local quotes

Get this fixed by a local pro

Free, no-obligation quotes from licensed HVAC technicians in your area. Compare up to 3 estimates before anyone visits.

Get free local quotes

Lennox furnace code E240: what it means

Lennox Code E240 indicates low flame current in run mode — the control board is sensing a flame during a normal heating cycle, but the microamp signal it reads through the flame sensor is below the minimum threshold the board expects.

The flame sensor (a metal rod in the burner flame) works by flame rectification: when the burner is lit, a tiny DC current flows from the rod, through the flame, to ground. The SureLight board measures that current in microamps. When the flame is present but the signal is weak, the board flags E240 rather than a full ignition failure.

The two documented triggers are a dirty or oxidized flame sensor and a weak or lifting flame. This is different from a no-flame lockout — the flame is being detected, just poorly.

What the board does next — keep running while it watches the signal, retry, or shut down and lock out — depends on the control revision in your furnace. The same is true of whether E240 self-clears once the signal recovers or holds until power is cycled. The behavior for your specific board is described in the installation instructions and on the diagnostic label on the unit, so check those rather than assuming a sequence.

Lennox furnace code E240: common causes, ranked by probability

  1. Dirty or oxidized flame sensor — carbon, dust, or oxide film on the sensor rod reduces the microamp signal. This is by far the most common cause and the first thing a technician checks.
  2. Weak, small, or lifting flame — poor combustion, low gas pressure, or partially blocked burners produce a flame that doesn’t fully envelop the sensor rod, lowering the current.
  3. Poor sensor ground or corroded connection — a loose sensor wire, corroded terminal, or bad chassis ground weakens the rectified signal path.
  4. Cracked sensor insulator or degraded sensor rod — an aging sensor with a hairline crack or eroded rod reads low even when clean.
  5. Marginal control board flame-sense circuit — least common; the board’s own sensing circuit drifts and misreads the current. Confirmed only after the sensor and flame are verified good.

How to fix Lennox furnace code E240: safe checks first

These are the only steps a homeowner should perform:

Do not open the burner compartment, clean the flame sensor, or touch any wiring — that is technician work.

How a technician will diagnose it

A qualified tech will typically:

  1. Pull the E240 history and any accompanying codes from the SureLight board.
  2. Put the furnace through a heat cycle and measure flame current in microamps with a meter in series with the sensor lead, comparing the reading to the minimum microamp value printed on your unit’s wiring diagram.
  3. Remove and clean or replace the flame sensor, then re-measure the signal.
  4. Inspect the flame quality — checking for a crisp blue flame that fully covers the sensor rod, and looking for lifting or yellow tipping.
  5. Check manifold and inlet gas pressure and clean or inspect the burners if the flame is weak.
  6. Verify the sensor ground and wiring continuity back to the board.
  7. Only if all of the above pass, evaluate the control board’s sense circuit.

You can sanity-check a quote: a legitimate E240 diagnosis almost always starts with a microamp reading and a sensor cleaning — not an immediate board replacement.

Symptom, cause and what to do

SymptomLikely causeDIY actionTechnician job
E240 shows but furnace still heatsDirty/oxidized flame sensorReplace filter; try one resetMeasure microamps, clean or replace sensor
E240 then short-cycling or dropoutWeak or lifting flameCheck registers openCheck gas pressure, clean burners, inspect flame
E240 recurs right after resetPoor sensor ground/connectionStop resetting; call techInspect and repair sensor wiring and ground
E240 followed by a shutdown or lockout codeFlame current fell below the board’s minimum and stayed thereOne reset only, then callMeasure microamps, clean or replace sensor, verify flame and gas pressure
E240 with clean sensor and good flameMarginal board sense circuitNoneVerify circuit, replace control board if confirmed

Lennox furnace code E240 repair cost

Honest US ranges (parts + labor; regional and model variation applies):

Most E240 calls resolve at the low end — a clean or new flame sensor. Be skeptical of a board-replacement quote before a microamp reading and sensor cleaning have been done.

Lennox code assignments are not consistent across the product line: the variable-speed controls (such as SLP98 and EL296) and the older two-stage SureLight boards use different code lists, and the formats differ too — some codes appear with a letter prefix, some without. For that reason this page does not publish meanings for other codes, because a meaning that is correct on one board revision can be wrong or nonexistent on another.

If your furnace is showing another code alongside E240:

Safety first: anything beyond filters, batteries, and visual checks on gas-burning equipment should be handled by a licensed technician. Repeatedly resetting a locked-out unit can mask a dangerous fault. When in doubt, get a pro.

Frequently asked questions

Is Lennox Code E240 dangerous?

It is not usually an immediate hazard, but it means the flame signal is weak while the burner runs. If ignored it can progress to a lockout and no heat, so book a technician soon.

Can I fix E240 by cleaning the flame sensor myself?

No. Cleaning the flame sensor means opening the burner compartment and handling internal components, which is technician work. Homeowners are limited to filters, thermostat and one reset.

Will E240 clear on its own?

That depends on the control revision in your furnace — some boards clear the code if flame current recovers, others hold it until power is cycled, and a persistent weak signal can end in a lockout. Your unit's literature describes the behavior for your specific board. A single power cycle is the only reset a homeowner should attempt.

Why does E240 come back after a reset?

A reset does not fix the root cause. A dirty or oxidized flame sensor, a weak or lifting flame, or low gas pressure will trigger E240 again until a technician cleans or corrects the actual fault.

Different code on your furnace? Look it up — and if we haven't covered it yet, telling us is how it gets written next.