Rheem Furnace Pressure Switch Stuck Open: Causes & Fixes

Last updated Oct 3, 2026 · By fixme.vip Editorial

Rheem Furnace: Pressure switch stuck open
Applies to: Rheem and Ruud gas furnaces with an induced-draft inducer motor and pressure switch, including 80% and 90%+ condensing models (e.g. R801, R802, R92, R96, R97 series). The flash pattern for this fault depends on the control board. On many Rheem boards it is 2 flashes, but check the code chart on your unit's door. Condensing models have more condensate-related causes.
Typical repair cost: $0 DIY – $1,200+ if the inducer motor or control board needs replacement — compare free local quotes

Get this fixed by a local pro

Free, no-obligation quotes from licensed HVAC technicians in your area. Compare up to 3 estimates before anyone visits.

Get free local quotes

Rheem furnace pressure switch stuck open: what it means

Before your Rheem furnace lights, the control board starts the inducer motor. The inducer creates a draft through the heat exchanger and vent pipe. A pressure switch senses that draft through a small rubber hose. When the draft is strong enough, the switch closes and tells the board it is safe to start ignition.

“Pressure switch stuck open” means the board started the inducer, but the switch never closed. As a safety measure, the furnace will not start the igniter or open the gas valve.

This is different from the opposite fault, “pressure switch stuck closed.” That code means the switch was already closed before the inducer started, which usually points to a failed switch or a wiring fault.

The flash pattern varies by control board. On many Rheem and Ruud boards it is 2 flashes. Always confirm it against the code chart on the inside of the blower door.

How the fault resets:

Rheem furnace pressure switch stuck open: common causes, ranked by probability

Technicians typically check venting and draft first, then hoses and condensate, then the inducer, and finally the switch and board.

  1. Blocked or restricted vent or combustion-air pipe. Common blockages include snow, ice, leaves, bird or wasp nests, and frost on the PVC vent pipes outside a condensing furnace. A vent pipe that is too long or has too many elbows can also prevent enough draft.
  2. Water in the condensate trap, inducer housing, or pressure-switch hose (90%+ models). A clogged trap, or a hose with a sag where water collects, blocks the pressure signal. This is one of the most common causes on condensing Rheem furnaces.
  3. Cracked, loose, kinked, or brittle pressure-switch hose, or a plugged port on the inducer housing.
  4. Weak or failing inducer motor. Worn bearings, a damaged inducer wheel, or a motor that runs too slowly will not create enough draft to close the switch.
  5. Failed pressure switch. The diaphragm may be ruptured or the contacts may be bad. This is less common than the causes above.
  6. Wiring or control board fault. A loose connector at the switch, or a board that doesn’t read the closed switch correctly. This is the least common cause.

How to fix Rheem furnace pressure switch stuck open: safe checks first

How a technician will diagnose it

  1. Confirm the fault. The tech reads the flash code and watches a heat cycle to confirm the inducer runs but the switch never closes.
  2. Inspect the venting. The tech checks the vent and intake pipes for blockages, sagging sections, and correct length and elbow count.
  3. Inspect hoses and drainage. The tech checks the switch hose and housing ports. On condensing models, they also check the condensate trap and drain path, and clean or flush them.
  4. Measure the draft. Using a manometer, the tech measures the draft the inducer produces and compares it to the setpoint printed on the switch. A low reading points to a vent, condensate, or inducer problem. A good reading points to the switch.
  5. Test the switch and wiring. If the draft is good, the tech checks the switch for continuity and checks the wiring and voltage at the board.
  6. Replace the faulty part. The tech replaces only the part that failed, using the exact-match Rheem part. The pressure switch rating is model-specific.

When reviewing a quote, ask for the manometer reading compared with the switch rating. If a tech replaces the switch without measuring draft, it is often a guess.

Symptom, cause and what to do

SymptomLikely causeDIY actionTechnician job
Inducer hums, no ignition, after snow or freezing weatherIced or snow-blocked vent or intakeClear the outside terminations, then do one resetCheck the vent pitch and termination clearances
Gurgling sound, code on a 90%+ furnaceWater in the trap, hose, or inducerCheck that the drain line and pump aren’t blockedClean the trap, re-route the hose, flush the drain
Code appears intermittentlyCracked hose or a marginal draftNone beyond the outdoor vent checkReplace the hose, measure draft with a manometer
Inducer is noisy, rattles, or runs slowlyInducer bearings or wheel failingCall for serviceReplace the inducer assembly
Inducer sounds normal, vents are clearFailed pressure switch or wiringCall for serviceTest the switch and wiring, replace the switch
Code persists with good draft and a good switchControl board faultCall for serviceDiagnose and replace the board

Rheem furnace pressure switch stuck open repair cost

Prices are typical US ranges. Expect to pay more for after-hours visits and older or discontinued models.

Safety first: anything beyond filters, batteries, and visual checks on gas-burning equipment should be handled by a licensed technician. Repeatedly resetting a locked-out unit can mask a dangerous fault. When in doubt, get a pro.

Parts & tools for this fix

As an Amazon Associate, fixme.vip earns from qualifying purchases. Prices and availability are on Amazon.

Frequently asked questions

Does a Rheem pressure switch stuck open fault reset by itself?

The board keeps retrying while the call for heat continues. If the switch closes, for example after ice melts off a vent, the furnace can start on its own. If the fault persists, many Rheem boards go into a timed lockout. They may retry after about an hour, or you can clear it by cycling power. The exact behavior depends on the board, so check the label on your unit.

Can I bypass or jumper the pressure switch to get heat?

No. The pressure switch confirms that combustion gases are being drawn out and vented outside. If you bypass it, the furnace can run with a blocked flue and push carbon monoxide into your home. A technician should find the real cause.

Is a stuck-open pressure switch usually a bad switch?

Usually not. Most of the time the switch is working correctly and reporting a real problem. Common examples are a blocked vent pipe, water in the condensate trap or hoses, a cracked hose, or a weak inducer motor. Technicians should test those before replacing the switch.

Why does my furnace hum and then stop without lighting?

That hum is usually the inducer motor starting. The board waits for the pressure switch to close. If the switch never closes, the board shuts the inducer off and never opens the gas valve or starts the igniter. It then flashes the pressure switch open code.